Constant Torque
Notes:
(*1) Indicated capacities are at the rated output voltage 230V for the 230V series and 460V for the 460V series. The rated capacity will be lowered
if the supply voltage is lower.
(*2) In the case of a low impedance load, such as a high-frequency motor, the current may drop below the rated value.
(*3) The output voltage cannot exceed the input supply voltage.
(*4) The taps within the inverter must be changed for an input power supply rated at 380 to 398V/50 Hz or 380 to 30V/60 Hz.
(*5) If the imbalance between phases exceeds 2%, use a power-factor correcting DC reactor(DCR). Please refer to the equation on the next page.
(*6) The test was conducted under the standard load conditions stipulated by the JEMA committee (at the load equivalent to 85% of the
nominal applied motor hp).
(*7) Indicates the values required when using a power factor correcting DC reactor (DCR) with a loaded nominal applied motor
(optional for inverters of 75 hp/CT, 100 hp/VT or less).
EQ5 AC Drive Operations Manual
_________________________________________________________________________
TECO – Westinghouse Motor Company Standard Specifications Notes con’t 105
EQ5 CT (Constant Torque) – 460V Series
Type
NEMA 1
PROTECTED CHASSIS
Applied Motor
Nominal (HP)
0.5 1 2 3 5 5 7.5 10 15 20 25 30 30 40 50 60 75 100 125 150200 250 300 350 350400 450500 600
Model
EQ5-4XXX-XX
0P5
-N1
001
-N1
002
-N1
003
-N1
005
-N1
007
-N1
010
-N1
015
-N1
020
-N1
025
-N1
030
-N1
032
-N1
040
-C
050
-C
060
-C
075
-C
100
-C
125
-C
150
-C
200
-C
250
-C
300
-C
350
-C
400
-C
450
-C
500
-C
600
-C
700
-C
800
-C
Rated output
capacity [kVA] (*1)
1.2 2.0 2.9 4.4 7.2 7.2 10 14 19 24 31 36 36 48 60 73 89 120140 167202 242 300 331 331414 466518 590
Rated output
current
㩷 [A] (*2)
1.5 2.5 3.7 5.5 9 9 13 18 24 30 39 45 45 60 75 91 112150 176 210253 304 377 415 415520 585650 740
Overload
capability
150% of rated output current for 1 min.
200% of rated output current for 0.5 s
150% of rated output current for 1 min.
180% of rated output current for 0.5 s
Starting torque minimum 200% (torque vector control mode) minimum 180% (torque vector control mode)
Output
ratings
Rated output
Voltage [V] (*3)
3-phase, 380V, 400V, 415V(440V)/50Hz, 380V, 400V, 440V, 460V/60Hz
Rated output
frequency [Hz]
50,60Hz
Input ratings
Phases, voltage,
frequency
3-phase,380 to 480V,50/60Hz 3-phase, 380 to 440V, 50/60Hz (*5)
㩷
Voltage/frequency
variations
Voltage: +10% to -15% (Imbalance rate between phases: 2% or less) (*5) , Frequency: +5% to -5%
Momentary
voltage dip
capability (*6)
Operation will continue with 310V or more. If voltage drops below 310V, operation will continue for up to 15 ms.
If "Continuous operation" is selected, the output frequency will be lowered to withstand the load until normal voltage is resumed.
Required power
supply capacity
[kVA] (*7)
0.7 1.2 2.2 3.1 5.0 5.0 7.2 9.7 15 20 24 29 29 38 47 57 70 93 111136 161 196 244 267 267341 383433 488
EQ5 VT (Variable Torque) – 460V Series
Type
NEMA 1
PROTECTED CHASSIS
Applied Motor
Nominal (HP)
0.5 1 2 3 5 7.5 10 15 20 25 30 30 40 50 60 75 100 125 150 200250 300 350 400 450500 600700 800
Model
EQ5-4XXX-XX
0P5
-N1
001
-N1
002
-N1
003
-N1
005
-N1
007
-N1
010
-N1
015
-N1
020
-N1
025
-N1
030
-N1
032
-N1
040
-C
050
-C
060
-C
075
-C
100
-C
125
-C
150
-C
200
-C
250
-C
300
-C
350
-C
400
-C
450
-C
500
-C
600
-C
700
-C
800
-C
Rated output
capacity [kVA] (*1)
1.2 2.0 2.9 4.4 7.2 10 13 18 24 29 35 36 48 60 73 89 120 140167 202242 300 331 386 414518 590669 765
Rated output
current
㩷
[A] (*2)
1.5 2.5 3.7 5.5 9 12.5 16.5 23 30 37 44 45 60 75 91 112 150 176210 253 304 377 415 485 520650 740840 960
Overload
capability
110% of rated output current for 1 min.
Starting torque 50% or more
Rated output
voltage [V] (*3)
3-phase, 380V, 400V, 415V(440V)/50Hz, 380V, 400V, 440V, 460V/60Hz
Rated output
frequency [Hz]
50,60Hz
Phases, voltage,
frequency
3-phase,380 to 480V,50/60Hz 3-phase, 380 to 440V, 50/60Hz (*4)
㩷
Voltage/frequency
variations
Voltage: +10% to -15% (Imbalance rate between phases: 2% or less) (*5) , Frequency: +5% to -5%
Momentary
voltage dip
capability (*6)
Operation will continue with 310V or more. If voltage drops below 310V, operation will continue for up to 15 ms.
If "Continuous operation" is selected, the output frequency will be lowered to withstand the load until normal voltage is resumed.
Required power
supply capacity
[kVA] (*7)
0.7 1.2 2.2 3.1 5.0 7.2 9.7 15 20 24 29 29 38 47 57 70 93 111 136 161 196 244 267 341 383433 488549 610
(*1) Indicated capacities are at the rated output voltage 230V for the 230V series and 460V for the 460V series.
㩷 The rated capacity will be lowered if the
supply voltage is lower.
(*2) In the case of a low impedance load, such as a high-frequency motor, the current may drop below the rated value.
(*3) The output voltage cannot exceed the input supply voltage.
Cont.
Output
ratings
Input ratings
EQ5 AC Drive Operations Manual
_________________________________________________________________________
TECO – Westinghouse Motor Company Standard Specifications Notes con’t 104
8. Specifications
8-1 Standard Specifications
EQ5 CT (Constant Torque) – 230V Series
Type NEMA 1 PROTECTED CHASSIS
Applied Motor
Nominal (HP)
0.25 0.5 1 2 3 5 5 7.5 10 15 20 25 30 30 40 50 60 75 100 125
Model
EQ5-2XXX-XX
0P2
-N1
0P5
-N1
001
-N1
002
-N1
003
-N1
005
-N1
007
-N1
010
-N1
015
-N1
020
-N1
025
-N1
030
-N1
032
-N1
040
-C
050
-C
060
-C
075
-C
100
-C
125
-C
150
-C
Rated output
capacity [kVA] (*1)
0.6 1.2 2.0 3.2 4.4 6.8 6.8 10 13 18 24 29 35 35 46 58 72 86 113 138
Rated output
current [A] (*2)
1.5 3.0 5.0 8.0 11 17 17 25 33 46 59 74 87 87 115 145 180 215 283 346
Overload
capability
150% of rated output current for 1 min.
200% of rated output current for 0.5 s
150% of rated output current for 1 min.
180% of rated output current for 0.5 s
Starting torque minimum 200% (torque vector control mode) minimum 180% (torque vector control mode)
Output
ratings
Rated output
voltage [V] (*3)
3-phase, 200V/50Hz, 200V,220V,230V/60Hz
Rated output
frequency [Hz]
50,60Hz
Input ratings
Phases, voltage,
frequency
zH06/05 ,V032 ot 002 ,esahp-3 3-phase, 200 to 230V, 50/60Hz
Voltage/frequency
variations
Voltage: +10% to -15% (Imbalance rate between phases: 2% or less) (*5) , Frequency: +5% to -5%
Momentary voltage
dip capability (*6)
Operation will continue with 165V or more. If voltage drops below 165V, operation will continue for up to 15 ms.
If "Continuous operation" is selected, the output frequency will be lowered to withstand the load until normal voltage is resumed.
Required power
supply capacity
[kVA] (*7)
0.4 0.7 1.3 2.2 3.1 5
5 7.2 9.7 15 20 24
29 29 38 47 56 69 93 111
EQ5 VT (Variable Torque) – 230V Series
Type NEMA 1 PROTECTED CHASSIS
Applied Motor
Nominal (HP)
0.25 0.5 1 2 3 5 7.5 10 15 20 25 30 30 40 50 60 75 100 125 150
Model
EQ5-2XXX-XX
0P2
-N1
0P5
-N1
001
-N1
002
-N1
003
-N1
005
-N1
007
-N1
010
-N1
015
-N1
020
-N1
025
-N1
030
-N1
032
-N1
040
-C
050
-C
060
-C
075
-C
100
-C
125
-C
150
-C
Rated output
capacity [kVA] (*1)
0.6 1.2 2.0 3.2 4.4 6.8 8.8 12 17 22 27 31 35 46 58 72 86 113 138 165
Rated output
current [A] (*2)
1.5 3.0 5.0 8.0 11 17 22 29 42 55 68 80 87 115 145 180 215 283 346 415
Overload
capability
110% of rated output current for 1 min.
Starting torque 50% or more
Output
ratings
Rated output
voltage [V] (*3)
3-phase, 200V/50Hz, 200V,220V,230V/60Hz
Rated output
frequency [Hz]
50,60Hz
Input ratings
Phases, voltage,
frequency
zH06/05 ,V032 ot 002 ,esahp-3 3-phase, 200 to 230V, 50/60Hz
Voltage/frequency
variations
Voltage: +10% to -15% (Imbalance rate between phases: 2% or less) (*5) , Frequency: +5% to -5%
Momentary voltage
dip capability (*6)
Operation will continue with 165V or more. If voltage drops below 165V, operation will continue for up to 15 ms.
If "Continuous operation" is selected, the output frequency will be lowered to withstand the load until normal voltage is resumed.
Required power
supply capacity
[kVA] (*7)
0.4 0.7 1.3 2.2 3.1 5 7.2 9.7 15 20 24
29 29 38 47 56 69 93 111 139
*See notes 1 - 7 on the next pages.
EQ5 PAGE 3