8. If a condensate neutralizer kit is installed with the appliance, check the assembly when cleaning the condensate trap, and replenish
the limestone chips if necessary. When replacing the limestone chips, take care to ensure chips are no smaller than ½” to avoid
blockage in condensate piping (for piping details, refer to condensate neutralizer installation instruction.)
9. Check condensate piping for sagging and/or leakage. Repair any sags or leaks before restoring power to the appliance.
It is very important that the condensate piping be no smaller than ¾”. To prevent sagging and maintain pitch, condensate piping should
be supported with pipe supports, and pitched ¼” per foot to allow for proper drainage.
The condensate line must remain unobstructed, allowing free flow of condensate. If condensate freezes in the line, or if line is
obstructed in any other manner, condensate can exit from the tee, resulting in potential water damage to property.
10. If the appliance has a condensate pump, ensure the pump operates properly before considering maintenance complete.